10.2 Adding setting groups
GUID-9C636C53-898E-4A60-9DDA-1DB13A65EE30 v3
In order to show for a DNP master which setting group is used, the procedure
outlines here can be performed.
In this example, only setting groups one and two are used. The DNP master will
get two binary inputs: the first is set if setting group one is used, the second is set if
setting group two is used.
1. Configure ACTVGRP (Basic IED functions) and SP16GAPC (Monitoring)
with the Application Configuration Tool (ACT).
IEC11000423-3-en.vsd
ACTVGRP
ACTGRP1
ACTGRP2
ACTGRP3
ACTGRP4
ACTGRP5
ACTGRP6
GRP1
GRP2
GRP3
GRP4
GRP5
GRP6
SETCHGD
REMSETEN
SP16GAPC
BLOCK
GRP1
^IN3
GRP2
^IN2
^IN3
^IN4
^IN5
^IN6
^IN7
^IN8
^IN9
^IN10
^IN11
^IN12
^IN13
^IN14
^IN15
^IN16
ACTVGRP
IEC11000423 V3 EN-US
Figure 91: Application configuration tool
To make it easier to recognize the signals for the active setting
group, user-defined names are used.
2. Open the Communication Management Tool (CMT). Set the Signal Type to
Binary Input Object, and choose the connection of the master for which the
values should be presented.
Section 10 1MRK 511 398-UEN C
DNP3 communication engineering
138 670 series 2.2 IEC
Engineering manual