The IEC 61850 structure mapping list displays the FPN objects based on the
current selection in the plant structure. The list may display either IEDs or data
attributes. The FPN object’s name is displayed in the column on the left and the
mapped PCM600 internal object name is displayed in the column on the right. The
IEC 61850 structure mapping displays customer data structure and customer data
attribute on the left; internal data structure and internal data attribute on the right.
Object Properties
Object properties window displays properties of objects currently selected in the
FPN Mappings and Internal Data Attribute lists. The properties are read-only and
cannot be modified by user.
11.1.2 IED and Signal Naming Convention
GUID-9432AA02-F2F5-4CEE-BCD3-D47713A60345 v2
The names used for the internal objects can be defined to be either the names used
in PCM600 or the names defined in the internal IEC 61850 model. To change the
naming convention, select PCM600 naming style in use from options.
11.2 Importing the System Configuration Description file
GUID-897210DF-7BC8-4A49-B567-EBEF3DAAF2C6 v1
Before starting the IEC 61850 Structure Mapping Tool, enable the option Import as
Flexible Product Naming SCD.
IEC17000021-1-en.vsdx
IEC17000021 V1 EN-US
Figure 103: Enabling FPN option
System Configuration Description (SCD) file can only be imported only at the
substation level.
1. Right click on a substation level.
2. Select and click Import from the Menu.
Section 11 1MRK 511 398-UEN C
Flexible product naming
146 670 series 2.2 IEC
Engineering manual