IEC16000190 V1 EN-US
Figure 78: ACT: Connect to GOOSE dialog window with Extended Mode
Receiver IED
Receiver IED list displays the Receiver IED Main Application, function block and
signal data. Connection can be made at signal level and one connection per signal.
Search
Main Application name, function block name and signal name are considered as
filtering.
8.4.2 Enable Easy GOOSE Engineering in PCM600
GUID-65A0F83C-522C-4920-AA2D-479A640ECE28 v1
1. Select Tools/Options
2. In Options/Application Configuration, open the “Configuration” tab
3. Under the “GOOSE configuration” section, check “Allow configuring
GOOSE in Application Configuration”.
4. Click “OK” to exit.
1MRK 511 398-UEN C Section 8
IEC 61850 communication engineering
670 series 2.2 IEC 119
Engineering manual