11.3 Starting the IEC 61850 Structure Mapping Tool
GUID-3216206E-D6FF-4BCE-9A85-CD4DBE4B5F51 v2
The tool can be started from any node from Substation to IED level.
1. Right click on one of the nodes.
2. Select Flexible Product Naming from the menu.
3. Click on IEC 61850 Structure Mapping.
The FPN object’s name is displayed in the column on the left and the name of
the mapped PCM600 internal object is displayed in the column on the right.
IEC17000024-1-en.vsdx
IEC17000024 V1 EN-US
Figure 106: Flexible product naming tool
11.4 IEC 61850 Structure Mapping
11.4.1 IED mapping
GUID-6588A7B6-5075-4FBE-9CE1-140A27AE8995 v2
The first step in the IEC 61850 structure mapping is to map the real IEDs to the
customer specific IEDs. IED mapping means that each server IED in the FPN
model is mapped with a corresponding IED in the internal PCM600 model, that is,
the real device in the substation. A server IED is an IED that has an access point
containing a server. IED mapping does not map the data attributes between the
IEDs unless the data attribute mapping is complete. IED mapping can be done in
the PCM600 plant structure and in the IEC 61850 structure mapping tool.
Section 11 1MRK 511 398-UEN C
Flexible product naming
148 670 series 2.2 IEC
Engineering manual

Table of Contents

Other manuals for ABB Relion 670 series