IEC08000338-2-en.vsd
IEC08000338 V2 EN-US
Figure 101: CMT: Select Class window
10.4.1 Configuring DNP3 class
GUID-B46924F8-B960-4B79-8EB8-4DFADABDFB10 v1
In DNP3 the user classifies the signals and defines those signals that are not
member of any class. CMT has a default predefined organization of classes per
signal type. In the master station the classes can be polled in sequences according
to the demands in the project. Unsolicited reporting is possible as well.
Modify the organization of the classes for each signal individually.
Procedure
1. Click in the Class field of the signal. A new window Select Class opens where
the user classifies the signal.
2. Select the signal classes and choose between None and 0 to 3 according to the
project demands.
3. Click OK to set the signal classification.
4. Write to IED.
1MRK 511 398-UEN C Section 10
DNP3 communication engineering
670 series 2.2 IEC 143
Engineering manual