1. Close PCM600 before running the IED connectivity package installation.
2. Install the IED series Connectivity package base.
3. Select and install the IED modules as required.
4. Install the documentation.
Installing 670 2.1.5 (or lower) version of the Connectivity package
on top of the 670 3.2.0.0 Connectivity package will corrupt the
Connectivity package installation. To work around this, uninstall all
the Connectivity packages (starting from the lowest version first),
and then install the 670 3.2.0.0 Connectivity package freshly again.
Because of parallel Connectivity package support, 670 3.2.0.0
Connectivity package will background install 670 3.1.2.0, 670
3.0.2.0, 670 2.1.6 and 670 2.1.5 Connectivity packages.
4.3 Setting technical key
GUID-6E273043-7AC6-4262-9522-ED24D8E31E93 v9
Both IED and an IED object in PCM600 have a technical key. The purpose of the
technical key is to prevent writing a configuration to wrong IED. The technical key
in the IED and PCM600 must be the same, otherwise it is not possible to write a
configuration. Each IED in a PCM600 project must have a unique technical key. It
is therefore not possible to set the same technical key for several IEDs in the same
PCM600 project.
For details on technical key settings, see Naming conventions for
IEC 61850
The technical key property in PCM600 corresponds to the IED
name attribute in SCL files. Avoid changing the IED name attribute
outside PCM600, because data in PCM600 might be lost when
importing SCL files.
When using PCM600 for writing to the IED, it is important that the
LHMI is not in a position where settings can be made. Only one
active transaction, from LHMI or PCM600, is allowed at any one
time.
When writing a configuration to the IED, PCM600 checks if the technical key
matches between the IED object in PCM600 and the physical IED. For
communication between the IED and PCM600, the technical key must be the same.
Users have the option to read the technical key from the IED and update it to
Section 4 1MRK 511 398-UEN C
Setting up a project
34 670 series 2.2 IEC
Engineering manual