the maximum number of data sets, number of entries in a data
set and the number of report control blocks that can be used.
3. Add and/or reconfigure data sets. The configured IED includes a number of
predefined data sets, but it is possible to add additional data sets and/or
reconfigure default data sets according to the requirements.
Reporting data sets only contain data intended to be used by
vertical clients, for example MicroSCADA or RTU560.
4. Configure report control blocks for each data set used in vertical
communication. Pre-configured IEDs include predefined report control blocks
which can be reconfigured. If additional control blocks are needed, it is
possible to add them according to requirements.
Up to 8 vertical clients can be configured.
5. Connect the report control blocks to vertical clients.
The vertical client must belong to the same sub-network as the
IEDs.
6. Export the SCD file.
Please see the IET600 user manual for additional information about
vertical and horizontal station communication engineering.
Procedure for horizontal engineering using IET600:
1. Create a project in IET600.
2. Import the SCD file exported from PCM600.
All data sets, report control blocks and GOOSE control blocks
must be located at LD0/LLN0. There are limitations regarding
the maximum number of data sets, number of entries in a data
set and the number of report control blocks that can be used.
3. Create a GOOSE data set for the sending IED. Define the content of the data
set according to the requirements.
1MRK 511 398-UEN C Section 8
IEC 61850 communication engineering
670 series 2.2 IEC 127
Engineering manual