Table 4: Merging units tab
Column Description Read only
MU Merging unit instance. Yes
Name Name of the merging unit. No
AP connection Associates Merging unit with the access point. This column
shows the access points that are available.
Changing this setting may have impact on
Application Configuration. When saving the
ECT configuration after associating a
merging unit to an access point creates the
merging unit reception module in the
background and removing association
removes the merging unit reception module.
These modules will appear in the plant
structure in HW configuration section and
will be available in ACT and SMT.
No
Sample value ID Sample value ID of the stream. No
The combination of associating merging units to access points
mentioned below is invalid.
For Merging units 9201 to 9208, if any five of the merging units are
associated to one access point and the remaining merging units are
assigned to different access points it will become an invalid
configuration.
1MRK 511 398-UEN C Section 5
Ethernet configuration tool
670 series 2.2 IEC 63
Engineering manual