EasyManua.ls Logo

ABB RER670 - Page 306

ABB RER670
506 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
hence the designation “reverse reactance” or “negative reactance”. Effectively this
means that, whereas the line voltage drop compensation in figure 126 gave a
voltage drop along a line from the busbar voltage U
B
to a load point voltage
U
L
,
the line voltage drop compensation in figure
129 gives a voltage increase (actually,
by adjusting the ratio X
L
/R
L
with respect to the power factor
, the length of the
vector U
L
will be approximately equal to the length of U
B
) from U
B
up towards the
transformer itself. Thus in principal the difference between the vector diagrams in
figure
126 and figure 129 is the sign of the setting parameter X
L
.
If now the tap position between the transformers will differ
, a circulating current
will appear, and the transformer with the highest tap (highest no load voltage) will
be the source of this circulating current. Figure
130 below shows this situation with
T1 being on a higher tap than T2.
IEC06000491_3_en.vsd
Load
T1
T2
U
B
UL
IT1
IT2
U
B
RIT1
jXLIT1
Icc
-Icc
(IT1+IT2)/2
IT1
IT2
RLIT2
jXLIT2
ICC...T2
ICC...T1
IL
IEC06000491 V3 EN-US
Figure 130: Circulating current caused by T1 on a higher tap than T2.
The circulating current I
cc
is predominantly reactive due to the reactive nature of
the transformers. The impact of I
cc
on the individual transformer currents is that it
increases the current in T1 (the transformer that is driving I
cc
) and decreases it in
T2 at the same time as it introduces contradictive phase shifts, as can be seen in
figure
130. The result is thus, that the line voltage drop compensation calculated
voltage U
L
for T1 will be higher than the line voltage drop compensation
calculated voltage U
L
for T2, or in other words, the transformer with the higher tap
position will have the higher
U
L
value and the transformer with the lower tap
position will have the lower U
L
value. Consequently, when the busbar voltage
increases, T1 will be the one to tap down, and when the busbar voltage decreases,
T2 will be the one to tap up. The overall performance will then be that the runaway
tap situation will be avoided and that the circulating current will be minimized.
Section 12 1MRK 506 375-UEN A
Control
300 Railway application RER670 2.2 IEC
Application manual

Table of Contents

Other manuals for ABB RER670

Related product manuals