Figure 135: Transformer with reverse reactance regulation and no circulating
current
The voltage DU=U
B
-U
L
=I
T
*Rline+j I
T
*Xline has the argument j2 and it is realised
that if j2 is slightly less than -90°, then U
L
will have approximately the same
length as U
B
regardless of the magnitude of the transformer load current I
T
(indicated with the dashed line). The automatic tap change control regulates the
voltage towards a set target value, representing a voltage magnitude, without
considering the phase angle. Thus, U
B
as well as U
L
and also the dashed line could
all be said to be on the target value.
Assume that we want to achieve that j
2
= -90°, then:
0
1 1
( )
90
0
1
0
1
90
90
j j
j j
U Z I
Ue Ze Ie ZIe
j j j
j
j j
j j
+
-
D = ´
ß
D = ´ =
ß
- = +
ß
= - -
EQUATION1938 V1 EN-US (Equation 76)
If for example cosj = 0.8 then j = arcos 0.8 = 37°. With the references in
figure
135, j will be negative (inductive load) and we get:
0 0 0
1
( 37 ) 90 53
j
= - - - = -
EQUATION1939 V1 EN-US (Equation 77)
1MRK 506 375-UEN A Section 12
Control
Railway application RER670 2.2 IEC 325
Application manual