- 62 -
4 - Operations
Parameter Denition Default Value Adjustable Ranges
SET TIME
Conn 1
Indicates the time the inverter takes to connect to the
grid for the rst time (not after grid fault).
30 sec 2 sec to
300 sec
SET TIME
Conn 2
Indicates the time the inverter takes to connect to the
grid after a grid fault.
300 sec 2 sec to
300 sec
DISABLE U>> Provides ability to enable/disable the absolute over
voltage set point U>>
Enable Disable or Enable
DISABLE U<< Provides ability to enable/disable the absolute under
voltage set point U<<
Enable Disable or Enable
DISABLE F>> Provides ability to enable/disable the absolute over fre-
quency set point F>>
Enable Disable or Enable
DISABLE F<< Provides ability to enable/disable the absolute under
frequency set point F<<
Enable Disable or Enable
DISABLE U> Provides ability to enable/disable the intermediate over
voltage set point U>
Enable Disable or Enable
DISABLE U>
(10 min)
Provides ability to enable/disable the parameter Set U>
(10 min)
Disable Disable or Enable
DISABLE U< Provides ability to enable/disable the intermediate under
voltage set point U<
Enable Disable or Enable
DISABLE F> Provides ability to enable/disable the intermediate over
frequency set point F>
Enable Disable or Enable
DISABLE F< Provides ability to enable/disable the intermediate under
frequency set point F<
Enable Disable or Enable
U>(10 min)
Der.
Provides ability to limit the power for 10 minutes due
to the high average voltage value set by the parameter
Set U>(10 min)
Disable Disable or Enable
Slow ramp Enable/disable the gradual feeding of power after the
grid connection
Enable Disable or Enable
OF Derating Enable/disable the power derating mode in the event of
grid over-frequency
Enable Disable or Enable
OF Der. Rest.
T
Set time of restart for power derating in the event of grid
over frequency
Enable Disable or Enable
Reset country
S
Resetting the “grid standard” selection time. Enable Disable or Enable