EasyManua.ls Logo

Autronica Autroprime - Add a New Unit to the Detection Loop; Remove a Loop Unit from the Detection Loop

Autronica Autroprime
86 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Changes on the Detection Loop
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME2-INSTAL/DGB, Rev. C, 2016-29-02,
Autronica Fire and Security AS
Page 78
14.5 Add a new unit to the detection loop
Scenario during normal operation / actions to be
carried out
Panel indication (visual/audible)
For example, an optical smoke detector BH-300 is added to the detection loop.
1 Enter service mode and disable the detection
loop in question.
2 Mount a new base on the detection loop.
3 Insert the new detector in its base.
4 Enable the detection loop. Observe Fault Warning “Configuration Mismatch”
5 Acknowledge all faults. Buzzer off, indicator to steady
6 Add the appropriate properties to the new unit
(Service Menu/Unit Configuration/Points).
7 In service menu, select System Settings/Save
Configuration-Restart System. Acknowledge
restart of system.
After restart of system observe quiescent condition on
panel.
8 From the menu check the loop topology. Observe that the topology is in accordance with the
new detector added.
14.6 Remove a loop unit from the detection loop
Scenario during normal operation / actions to be
carried out
Panel indication (visual/audible)
For example, an existing heat detector BD-300 is removed from the detection loop.
1 Enter service mode and disable the detection
loop in question.
2 Remove the detector from its base and repair
the cable break.
3 Enable the detection loop. Observe fault warning “Loop Unit not responding”
4 Acknowledge all faults. Buzzer off, indicator to steady
5 Enter service mode.
Select fault warning “Loop Unit not responding”.
6 Select function “ Remove Unit from
Configuration”.
7 In service menu, select System Settings/Save
Configuration, then Restart System.
After restart of system observe quiescent condition on
panel.
8 From the menu check the loop topology. Observe that the removed detector is no longer found
in the topology.

Table of Contents

Other manuals for Autronica Autroprime

Related product manuals