Observe DIN EN 60730 part 1.
Î Install a disconnecting device with at least a 3 mm contact
gap per pole to interrupt the power supply.
Î Protect power supply with a ground fault circuit interrupter,
nominal residual current I
FN
≤ 30 mA
Î Only use suitable pipe types according to regional
regulations.
Î Adjust minimum diameter of the electrical pipes to
accommodate the motor output and pipe length.
Î If hazardous situations can occur, provide an emergency off
switch according to DIN EN 809. The builder/operator must
make a decision according to this standard.
Pos: 47.11 /Tec hnische Dok umentation Sp eck Pumpen/B etriebsanleitung/ Installation/El ektrischer A nschluss/BADU Tr onic/Bauseitiger Anschluss Tro nic @ 8\mod_ 14751408733 52_370.docx @ 9 9001 @ @ 1
Î Connection by customer:
– Fuse protection 1 phase 230 V/3 phase 400 V safety fuse
10 A time delay
– Rated short circuit breaking capacity I
CN
≤ A
Î Black plug terminals and pins carry voltages up to 230 V.
Green plug terminals and pins may only be connected
potential-free.
Î Before voltage is connected to the control, all pin strips must
be occupied by the appropriate plug terminals.
Î Mains power supply (L,N) 230 V, 50/60 Hz (continuous
voltage)