Installation
03|2022 EN 43
Contact load
Z1, Z2 maximum 2 A, 250 V~ AC3
11, 12, 14 maximum 2 A, 250 V~ AC3
Connection load
Lp, Np maximum 4 A, 250 V~ AC3
Rocker switch
The rocker switch installed on the front turns the whole device on
and off.
The light on the rocker switch displays the operational readiness.
If the device is turned off, no contact information can be output via
Z1-Z2.
5.3.1 Replacing the fuses
There are two different fuses present.
• 4 A fuse for pumps with asynchronous motors
• 315 mA to safeguard the control unit’s circuit board
Pos: 47.20 /Tec hnische Dok umentation Sp eck Pumpen/B etriebsanleitung/ Installation/El ektrischer A nschluss/BADU Omnitronic/Klemmenplan @ 12\mo d_152569614 8798_370.docx @ 180987 @ 3 @ 1
5.3.2 Terminal connection table