7.3 Off-line Phase on Configuration Errors (LOS)
The AS-i masters with advanced diagnostics offer the possibility to put themselves
into the off-line Phase when a configuration error on the AS-Interface occurs. In
this way the security of the application can be ensured. The reaction to a configu-
ration error is very fast and the host can be relieved from this task. If there are any
problems on the AS-i network, the AS-interface can be switched to a secure state.
There are two different ways to parameterize the AS-i master for this feature:
• Every configuration error during normal operation in protected mode releases
the off-line phase.
• For each slave address can be chosen whether a configuration error on this ad-
dress will release the off-line phase or not. This information is stored in the List
of Off-line Slaves (LOS).
The user himself can decide how the system reacts to a configuration error on
the AS-Interface. The AS-i master can release the off-line phase in critical situ-
ations, i. e. only with certain slave addresses, while in less critical situations (if
one of the other AS-i slaves have a configuration error) only the error message
configuration error is sent to the host, but AS-i is still running.
The parameterization of off-line phase on configuration error is also supported by
the "AS-i Control Tools" from version 3.0 (command Master | Identity | Offline on
configuration error).