AS-i/PROFIBUS Gateway PROFIBUS-DP
Subject to reasonable modifications due to technical advances Copyright Bihl+Wiedemann, Printed in Germany
Bihl+Wiedemann GmbH · D-68199 Mannheim · Phone +49-621-339960 · Fax +49-621-3392239 · Internet http://www.bihl-wiedemann.de
issue date 7.1.2002
55
The following types are possible:
The consistency of the digital process data is ignored. At least each word of the
analog data has to be consistent. The mailbox commands have to be consistent.
The GSD file submits the corresponding entry.
The IDs can be used in different sequences. But in the I/O data field can only be
one area with each type.
Areas of the I/O-data fields
type input data
length (bytes)
output data
length (bytes)
00
16
empty 0…128 0…128
01
16
digital process data out of AS-i circuit 1 0…32 0…32
02
16
digital process data out of AS-i circuit 2 0…32 0…32
03
16
mailbox 2…36 2…34
10
16
analog input data circuit 1, slave 31 2…128 0
11
16
analog input data circuit 1, slave 15 2…120 0
12
16
analog output data circuit 1, slave 31 0 2…128
13
16
analog output data circuit 1, slave 15 0 2…120
14
16
analog input data circuit 2, slave 31 2…128 0
15
16
analog input data circuit 2, slave 15 2…120 0
16
16
analog output data circuit 2, slave 31 0 2…128
17
16
analog output data circuit 2, slave 15 0 2…120