8.9 Analog Current Input
AD Analog/digital converter
Fig. 8-33: Analog Current Input
Data Unit Min. Typ. Max.
Allowed input current mA 0 +35
Working range input current I
on_work
mA 0 +20
Input resistance R
i
Ω 300
Input bandwidth (-3 dB) kHz 1,3
Common-mode range V -30 +30
Common-mode rejection dB 50
Resolution Bit
12
1)
11
2)
Cables For cable lengths > 30 m, only use
shielded cables.
1) Applies to: Optional I/O extension DA (X38)
2) Applies to: Control sections with extended scope CSx02.1B
(X35), CDB02.1B (X36)
Tab. 8-36: Analog Current Input