148 Brocade MLX Series and NetIron XMR Hardware Installation Guide
53-1003821-01
Installing a NetIron XMR 4000 router
3
DANGER
If the installation requires a different power cord than the one supplied with the router, make
sure you use a power cord displaying the mark of the safety agency that defines the regulations
for power cords in your country. The mark is your assurance that the power cord can be used
safely with the router.
4. For information about powering on the system, refer to Activating the power source” on
page 194.
Connecting DC power
You can provide DC power for the NetIron XMR 4000 router using a DC-to-DC power supply. DC
power must be supplied at 48 V and 40 A. The DC-to-DC supply provides the DC power to the router
at 12 V and 100 A.
DANGER
The procedure in this section is for qualified service personnel.
Follow these steps to connect DC power source:
NOTE
Due to multiple power supply vendors, the layout of the LEDs on your DC power supply may differ
from what is shown in Figure 99, but their function is the same.
1 Ground point 3 Cord retainer
2Power cord
1
2
3