3-5
T -296
3.3.9 Perishable Mode -- Economy
The economy mode is an extension of the conventional
mode and is applicable to units with two speed
evaporator fan motors. The modeis activated when the
settingoffunctioncodeCd34is “ON”.Economymodeis
provided for power saving purposes. Economy mode
could be utilized in the transportation of temperature
tolerant cargo or non-respiration items which do not
requirehighairflowforremovingrespiration heat. There
is no active display indicator that economy mode has
been activated. To check for economy mode, perform a
manual display of code Cd34.
In order to achieve economy mode, a perishable set
point must be selected prior to activation. When
economy mode is active, the evaporator fans will be
controlled as follows:
At the start of each cooling or heating cycle, the
evaporator fans will be run in high speed for three
minutes. They will then be switched to low speed any
time the supply air temperature is within ¦ 0.25_C
(0.45_F) of the set point and the return air temperature
isless thanor equalto thesupply air temperature + 3_C
(5.4_F). The fans will continue to run in low speed for
onehour.Atthe endof thehour ,theevaporator fanswill
switchbacktohighspeedandthecyclewillberepeated.
3.3.10 Perishable Mode -- Dehumidification
The dehumidification mode is provided to reduce the
humidity levels inside the container. The mode is
activated when a humidity value is set at at function
code Cd33. The display module SUPPLY led will flash
ON and OFF every second to indicate that the
dehumidification mode is active. Once the Mode is
active and the following conditions are satisfied, the
controller will activate the heat relay to begin
dehumidification.
1. The humidity sensor reading is above the set point.
2. The Supply air temperature is less than 0.25_C
above set point.
3. The heater debounce timer (three minutes) has
timed out.
4. Heater termination thermostat (HTT) is closed.
If the above conditions remain truefor at least one hour
the evaporator fans will switch from high to low speed
operation. The evaporator fan speed will switch every
hour thereafter as long as all conditions are met (see
Bulb Mode section for different evaporator fan speed
options). If any condition except for item (1) becomes
false OR if the relative humidity sensed is 2% below the
dehumidification set point, the high speed evaporator
fans will be energized.
In the dehumidification mode power is applied to the
defrost and drain pan heaters. This added heat load
causes the controller to open the suction modulating
valvetomatchtheincreasedheatloadwhile stillholding
the supply air temperature very close to the set point.
Opening the modulating valve reduces the temperature
of the evaporator coil surface, which increases the rate
at which water is condensed from the passing air.
Removing water from the air reduces the relative
humidity. When the relative humidity sensed is 2%
belowthesetpoint ,thecontrollerde-energizestheheat
relay. The controller will continue to cycle heating to
maintain relative humidity below the selected set point.
If the mode is terminated by a condition other than the
humidity sensor, e.g., an out-of-range or compressor
shutdown condition, the heat relay is de-energized
immediately.
T wo timers are activated in the dehumidification mode
topreventrapidcyclingandconsequent contactorwear .
They are:
1. Heater debounce timer (three minutes).
2. Out-of-range timer (five minutes).
The heater debounce timer is started whenever the
heater contactor status is changed. The heat contactor
remains energized (or de-energized) for at least three
minutes even if the set point criteria are satisfied.
The out-of-range timer is started to maintain heater
operation during a temporary out-of-range condition. If
the supply air temperature remains outside of the user
selectedin-range settingformorethanfiveminutes, the
heaters will be de-energized to allow the system to
recover. The out-of-range timer starts as soon as the
temperature exceeds the in-range tolerance value set
by function code Cd30.
3.3.11 Perishable, Dehumidification -- Bulb Mode
Bulbmodeis anextensionofthe dehumidificationmode
which allows changes to the evaporator fan speed
and/or defrost termination set points.
BulbmodeisactivewhenconfigurationcodeCd35isset
to“Bulb”.Oncethebulbmodeis activated,theusermay
then change the dehumidification mode evaporator fan
operationfrom the default(speed alternates from lowto
high each hour) to constant low or constant highspeed.
This is done by toggling function code Cd36 from its
default of “alt” to “Lo” or “Hi” as desired. If low speed
evaporator fan operation is selected, this gives the user
the additional capability of selecting dehumidification
set points from 60 to 95% (instead of the normal 65 to
95%).
In addition, if bulb mode is active, function code Cd37
may be set to override the previous defrost termination
thermostat settings. (Refer to paragraph 4.10.4) The
temperatureatwhichthedefrost terminationthermostat
will be considered “open” may be changed [in 0.1_C
(0.2_F) increments] to any value between 25.6_C
(78_F)and4_C(39.2_F). Thetemperatureatwhichthe
defrost termination thermostat is considered closed for
interval timer start or demand defrost is 10_C(50_F)for
“open values from 25.6_C down to a 10_C setting. For
“open” values lower than 10_C, the “closed” values will
decrease to the same value as the “open” setting.
Bulb mode is terminated when:
1. Bulb mode code Cd35 is set to “Nor.”
2. Dehumidification code Cd33 is set to “Off.”
3. The user changes the set point to one
that is in the frozen range.
When bulb mode is disabled by any of the above, the
evaporator fan operation for dehumidification reverts to
“alt”andtheDTSterminationsettingresetsto thevalue
determined by controller configuration variable CnF41.
3.3.12 Temperature Control -- Frozen Mode
With configuration variable CnF26 set to --10_ Cthe
frozen mode of operation is active with set points at or
below --10_C(+14_F).With thevariablesetto --5_C,the
frozen mode is active at or below --5_C(+23_F).
Downloaded from ManualsNet.com search engine