SECTION 5
TROUBLESHOOTING
CONDITION POSSIBLE CAUSE
REMEDY/
REFERENCE
SECTION
5.1 UNIT WILL NOT START OR STARTS THEN STOPS
External power source OFF Turn on
Start-Stop switch OFF or defective Check
o power to un
t
Circuit breaker tripped or OFF Check
Autotransformer not connected 4.2.2
Circuit breaker OFF or defective Check
Control transformer defective Replace
oss o
contro
power
Fuse (F3) blown Check
Start-Stop switch OFF or defective Check
Evaporator fan motor internal protector open 6.16
Condenser fan motor internal protector open 6.11
Component(s) Not Operating
Compressor internal protector open 6.8
High pressure switch open 5.7
Heat termination thermostat open Replace
Low line voltage Check
Com
ressor hums
but does not
Single phasing Check
,
start
Shorted or grounded motor windings 6.8
Compressor seized 6.8
5.2 UNIT OPERATES LONG OR CONTINUOUSLY IN COOLING
Hot load (Failure to Pre--cool) Normal
onta
ner
Defective box insulation or air leak Repair
Shortage of refrigerant 6.7.1
Evaporator coil covered with ice 5.6
Evaporator coil plugged with debris 6.15
Evaporator fan(s) rotating backwards 6.15/6.16
Defective evaporator fan motor/capacitor 6.17
Air bypass around evaporator coil Check
Refrigeration System
Controller set too low Reset
Compressor service valves or liquid line shutoff valve par-
tially closed
Open valves
completely
Dirty condenser 6.10
Compressor worn 6.8
Current limit (function code Cd32) set to wrong value 3.3.5
Suction modulation valve malfunction 6.18