CONDITION POSSIBLE CAUSE
REMEDY/
REFERENCE
SECTION
5.3 UNIT RUNS BUT HAS INSUFFICIENT COOLING
Compressor Compressor valves defective 6.8
Abnormal pressures 5.7
Controller malfunction 5.9
Evaporator fan or motor defective 6.16
e
r
gerat
on
ystem
Suction modulation valve malfunction 6.18
Condenser Pressure Transducer defective Check
Shortage of refrigerant 6.7.1
5.4 UNIT WILL NOT HEAT OR HAS INSUFFICIENT HEATING
Start-Stop switch OFF or defective Check
No operation of any kind
Circuit breaker OFF or defective Check
External power source OFF Turn ON
Circuit breaker or fuse defective Replace
Control T ransformer defective Replace
No control power
Evaporator fan internal motor protector open 6.16
Heat relay defective Check
Heater termination switch open 6.15
Heater(s) defective 6.15
Heater contactor or coil defective Replace
Evaporator fan motor(s) defective or rotating backwards 6.15/6.16
Unit will not heat or has insu
i-
Evaporator fan motor contactor defective Replace
cient heat
Controller malfunction 5.9
Defective wiring Replace
Loose terminal connections T ighten
Low line voltage 2.3
5.5 UNIT WILL NOT TERMINATE HEATING
Controller improperly set Reset
Controller malfunction 5.9
Heater termination thermostat remains closed along with
the heat relay
6.15
5.6 UNIT WILL NOT DEFROST PROPERLY
Defrost timer malfunction (Cd27) Table 3-5
Loose terminal connections T ighten/
Will not initiate defrost
Defective wiring Replace
automatically
Defrost temperature sensor defective or heat termination
thermostat open
Replace
Heater contactor or coil defective Replace
Will not initiate de
rost
Manual defrost switch defective Replace
manually
Defrost temperature sensor open 4.10.4
Initiates but relay (DR) drops
out
Low line voltage 2.3
Heater contactor or coil defective Replace
n
t
ates
ut
oes not
e
rost
Heater(s) burned out 6.15