EasyManuals Logo

Circutor CVM-A1500 User Manual

Circutor CVM-A1500
378 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #356 background imageLoading...
Page #356 background image
10.2.- RELAY DIGITAL INPUTS/OUTPUTS
General features
Maximum power of the module 3 W
Refresh time 1 s
Response time (outputs) / Detection time (inputs) < 150 ms
Relay digital outputs
(95)
Quantity 8
Maximum voltage, open contacts 250 V~
Maximum current 3 A
Maximum switching power 750 VA
Electrical working life (250 VAC / 3A) 10
5
cycles
Mechanical working life 2 x 10
7
cycles
Digital inputs
(95)
Quantity 8
Type Potential-free contact
Insulation 4 kV
Input impedance 32 kΩ
Environmental features
Operating temperature -10ºC ... +50ºC
Storage temperature -20ºC ... +80ºC
Relative humidity (without condensation) 5 ... 95%
Maximum altitude 2000 m
Protection degree
(96)
IP30
Mechanical features
Dimensions (mm) Figure 410
Weight 105 g
Enclosure V0 self-extinguishing plastic
Assembly Panel
(95)
Must be connected to SELV circuit.
(96)
This pollution degree hasn’t been tested by UL.
Standards
Safety requirements for electrical equipment for measurement, control
and laboratory use -- Part 1: General requirements
IEC/EN 61010-1:2010
(Third Edition)
Electromagnetic compatibility (EMC) -- Part 6-2: Generic standards - Im-
munity for industrial environments
UNE-EN 61000-6-2:2006
Electromagnetic compatibility (EMC) -- Part 6-4: Generic standards -
Emission standard for industrial environments
UNE-EN 61000-6-4:2007
Insulation coordination for equipment within low-voltage systems -- Part
1: Principles, requirements and tests�
IEC 60664-1:2007
Safety requirements for electrical equipment for measurement, control
and laboratory use -- Part 2-030: Particular requirements for testing and
measuring circuits
IEC 61010-2-030:2010
(First Edition)
Safety requirements for electrical equipment for measurement, control,
and laboratory use - Part 1: General requirements
UL 61010-1 3rd edition, 2012-
05
Safety Requirements for Electrical Equipment for Measurement, Control
and Laboratory Use - Part 1: General Requirements (Adopted IEC 1010-
1:1990 with modications)
CAN/CSA-C22.2 No. 61010-
1, 3rd edition, 2012-05
356
CVM-A1000 - CVM-A1500
Instruction Manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Circutor CVM-A1500 and is the answer not in the manual?

Circutor CVM-A1500 Specifications

General IconGeneral
BrandCircutor
ModelCVM-A1500
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals