EasyManua.ls Logo

Circutor CVM-A1500 - Page 357

Circutor CVM-A1500
378 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10.3.- ANALOGUE INPUTS/OUTPUTS
General features
Maximum power of the module 3W
Refresh time 1 s
Response time (outputs) / Detection time (inputs) < 150 ms
Analogue outputs
(97)
Quantity 8
Maximum internal voltage 12 V
Linearity <1%
DAC resolution 4096 dots
Analogue outputs in current mode
Nominal output range 0-20 mA or 4-20 mA (Programmable)
Maximum load resistor 300
Analogue outputs in voltage mode
Nominal output range 0-10 V
Minimum load resistor 5000
Analogue inputs
(97)
Quantity 4
Type of measurement Current
Nominal input range 0-20 mA or 4-20 mA (Programmable)
Accuracy <1%
Input impedance 150
Maximum acceptable input current
22 mA
Environmental features
Operating temperature -10ºC ... +50ºC
Storage temperature -20ºC ... +80ºC
Relative humidity (without condensation) 5 ... 95%
Maximum altitude 2000 m
Protection degree
(98)
IP30
Mechanical features
Dimensions (mm) Figure 410
Weight 80 g
Enclosure V0 self-extinguishing plastic
Assembly Panel
(97)
Must be connected to SELV circuit.
(98)
This pollution degree hasn’t been tested by UL.
Standards
Safety requirements for electrical equipment for measurement, control
and laboratory use -- Part 1: General requirements
IEC/EN 61010-1:2010
(Third Edition)
Electromagnetic compatibility (EMC) -- Part 6-2: Generic standards - Im-
munity for industrial environments
UNE-EN 61000-6-2:2006
Electromagnetic compatibility (EMC) -- Part 6-4: Generic standards -
Emission standard for industrial environments
UNE-EN 61000-6-4:2007
Insulation coordination for equipment within low-voltage systems -- Part
1: Principles, requirements and tests�
IEC 60664-1:2007
357
Instruction Manual
CVM-A1000 - CVM-A1500

Table of Contents

Related product manuals