11 750-265
Table 2. Wire Sizes.
Application Recommended Wire Size Recommended Part Number(s)
Maximum
Leadwire
Distance (in
feet)
Line Voltage
Terminals
14, 16, 18 AWG Copper
conductor, 600 volt
insulations, moisture-
resistance wire
TTW60C, THW75C, THHN90C 300
Remote Reset/
TOD
22 AWG two-wire twisted
pair, insulated for low voltage
Beldon 8443 or equivalent 1000
Temperature
(operating)
Sensors
22 AWG two-wire twisted
pair, insulated for low voltage
Beldon 8443 or equivalent 50
Temperature
(Limit) Sensors
22 AWG two-wire twisted pair
with ground.
Beldon 8723 shielded cable or equivalent 50
Flame Sensor
(Flame Rod/UV)
14, 16, 18 AWG Copper
conductor, 600 volt
insulations, moisture-
resistance wire
TTW60C, THW75C, THHN90C 30
Ignition Ignition Cable rated for 25kV
at 482F(250C)
32004766-001 (2') or -003 (per foot) 3
Grounding Earth ground (subbase and
relay module).
1. Use to provide a connection between the subbase and
the control panel of the equipment. Earth ground must be
capable of conducting enough current to blow the 20A
fuse (or breaker) in the event of an internal short circuit.
2. Use wide straps or brackets to provide minimum length,
maximum surface area ground conductors. If a leadwire
must be used, use 14 AWG copper wire.
3. Make sure that mechanically tightened joints along the
ground path are free of nonconductive coatings and pro-
tected against corrosion on mating surfaces.