833-3577 CB-FALCON SYSTEM OPERATOR INTERFACE
65-0296—01 48 750-241
ADVANCED SETUP
Pressing the ADVANCED SETUP button on the Setup page
displays more options that can be set by the user (Fig. 111).
Fig. 111. Advanced Setup.
Ethernet Settings
Ethernet Settings is used to enable Ethernet communications
for remote diagnostics, file transfers, and remote support, and
is not typically enabled (Fig. 112). This feature should remain
disabled unless directed to do so for remote troubleshooting.
Once the feature is enabled, the 833-3577 must be reset to
start it at power-up. The Ethernet interface can also be used
to transfer profile curve files to/from the 833-3577 over a local
intranet or the Internet.
Pilot test hold ON
OFF
21 24
Ignition
source
Hot Surface Igniter
External ignition
Internal ignition
Pilot type Direct burner ignition
Intermittent
Interrupted
Lightoff rate %
Preignition
time
0-600 seconds
0 = Not configured
Pilot Flame
Establishing
Period
15 secs
10 secs
4 secs
Igniter on
during
1st half of PFEP
Pilot Flame Establishing Period
Main Flame
Establishing
Period
15 secs
10 secs
5 secs
Flame
Threshold
μA/V
Ignite failure
delay
0-600 seconds
0 = Not configured
Ignite failure
response
Lockout
Continuous recycle
Recycle & hold
Recycle & lockout
Ignite failure
retries
3 or 5
MFEP flame
failure
response
Recycle
Lockout
Run flame
failure
response
Recycle
Lockout
NTC sensor
type
10k dual safety
12k single non-safety
22 27
Flame sensor
type
UV power tube
Flame rod
None
Modulation
output
4-20mA
0-10V
Fan PWM
Temperature
Units
Fahrenheit
Celsius
Anti short
cycle time
0-600 seconds
0 = Not configured
Alarm silence
time
0-600 minutes
0 = Not configured
Power up
with lockout
Clear lockout
Do NOT clear lockout
Table 42. Configurable Parameters. (Continued)
Parameter Comment
Table
#
Page
#
Absolute
maximum fan
speed
RPM 23 27
Absolute
minimum fan
speed
RPM
Fan gain
down
0-65535
Minimum
duty cycle
1-100%
Pulses per
revolution
1-10
PWM
frequency
1000
2000
3000
4000
Slow down
ramp
0-7000RPM/sec
Speed up
ramp
0-7000RPM/sec
Table 42. Configurable Parameters. (Continued)
Parameter Comment
Table
#
Page
#