Part No. 750-263 3-13
2. Stack design using direct vent combustion
6" Standard 4" 6" 75 75
4" Option 4" 4" 40 40
CFC750 6" Standard 4" 6" 40 40
8" Standard 6" 8" 60 60
6" Option 6" 6" 40 40
10" Option 6" 10" 70 70
10" Standard 6" 10" 40 40
8" Option 6" 8" 30 30
12" Option 6" 12" 45 45
12" Standard 6" 12" 30 30
10" Option 6" 10" 25 25
CFC 2500 12" Standard 8" 12" 100 100
* Each additional 90 elbow equals 5 equivalent feet of ductwork. Subtract from the maximum or
minimum length accordingly.
** Increasing the diameter of the air intake will reduce the pressure drop and thereby allow longer total
vent lengths.
CFC1500
CFC1800
Maximum allowable pressure drop in combustion air intake duct is - 0.25" w.c.
Boiler
CFC 500
CFC1000