Chapter 4 — CFC Commissioning
4-8 Part No. 750-263
Parameter Group Parameter Name Access
Min.
Range Default Setting Max. Range
Parameter
Units
Installation
Setting
Annunciation Configuration Annunciator 2 short name Service A2
Annunciation Configuration Annunciator 2 long name Service LOW WATER
Annunciation Configuration Annunciator 3 location Service Unused
Annunciation Configuration Annunciator 3 short name Service A3
Annunciation Configuration Annunciator 3 long name Service
AUXILIARY LOW
WATER
Annunciation Configuration Annunciator 4 location Service ILK
Annunciation Configuration Annunciator 4 short name Service A4
Annunciation Configuration Annunciator 4 long name Service
HIGH AIR
PRESSURE
Annunciation Configuration Annunciator 5 location Service ILK
Annunciation Configuration Annunciator 5 short name Service A5
Annunciation Configuration Annunciator 5 long name Service
HIGH GAS
PRESSURE
Annunciation Configuration Annunciator 6 location Service ILK
Annunciation Configuration Annunciator 6 short name Service A6
Annunciation Configuration Annunciator 6 long name Service
LOW GAS
PRESSURE
Annunciation Configuration Annunciator 7 location Service Unused
Annunciation Configuration Annunciator 7 short name Service A7
Annunciation Configuration Annunciator 7 long name Service Annunciator7
Annunciation Configuration Annunciator 8 location Service Unused
Annunciation Configuration Annunciator 8 short name Service A8
Annunciation Configuration Annunciator 8 long name Service Annunciator8
Annunciation Configuration PII short name Service PII
Annunciation Configuration PII long name Service Pre-Ignition ILK
Annunciation Configuration LCI short name Service LCI
Annunciation Configuration LCI long name Service
Load Control
Input
Annunciation Configuration ILK short name Service ILK
Annunciation Configuration ILK long name Service Interlock
Central Heat Configuration CH enable User Enabled
Central Heat Configuration CH demand source Service
Sensor & Stat
terminal
Central Heat Configuration CH sensor Service Outlet sensor
Central Heat Configuration CH setpoint User 32 150 194 °F
Central Heat Configuration CH TOD setpoint Service 32 120 194 °F
Central Heat Configuration CH on hysteresis Service 2 5 60 °F
Central Heat Configuration CH off hysteresis Service 2 15 60 °F
Central Heat Configuration CH outdoor reset enable Service Disabled
Central Heat Configuration CH P gain Service 0 50 400
Central Heat Configuration CH I gain Service 0 50 400
Central Heat Configuration CH D gain Service 0 0 400
Central Heat Configuration CH hysteresis step time Service 0 60 900 seconds
Outdoor Reset Configuration
CH ODR max. outdoor
temperature Service -40 80 140 °F
Outdoor Reset Configuration
CH ODR min. outdoor
temperature Service -40 0 140 °F
Outdoor Reset Configuration
CH ODR min. water
temperature Service 32 50 180 °F