Chapter 4 — CFC Commissioning
4-10 Part No. 750-263
*Access Levels:
Read Only = parameter not user-configurable
Service = password required (9220)
User = no password required
Parameter Group Parameter Name Access
Min.
Range Default Setting Max. Range
Parameter
Units
Installation
Setting
Anti-condensation
Configuration
DHW anti-condensation
setpoint Service 32 140 194 °F
Anti-condensation
Configuration
DHW anti-condensation
pump force off Service Disabled
Anti-condensation
Configuration
Anti-condensation > Outlet
limit Service No
Anti-condensation
Configuration Anti-condensation > Delta-T Service No
Anti-condensation
Configuration
Anti-condensation > Stack
limit Service No
Anti-condensation
Configuration
Anti-condensation > Slow
start Service Yes
Anti-condensation
Configuration
Anti-condensation > Forced
rate Service Yes
Lead Lag Configuration Lead Lag slave enable Service Disabled
Lead Lag Configuration Fan rate during off cycle Service 900 1500 6500 RPM
** Shaded parameters are Safety Parameters and require Verification and manual reset of the control prior to operation. Please refer to
Section A, "Changing parameter settings".