Command Line Interface 57
Commands
To get the current status for a specific unit, type:
To reset maximum current drawn, type:
currentprotection
Turns on and off the over current protection feature. The overcurrent
protection does not let any outlet be turned on if the current drawn by the unit
is greater than the current threshold configured with the command alarm. This
command can also be used to display the current protection status.
Syntax
currentprotection <status|on|off>
Arguments
status Displays the current protection status
on Enables over current protection
off Disables over current protection
Examples
To display current protection status for all units, type:
pm> current 2
IPDU #2: True RMS current: 2.4A. Maximum current:
10.2A
pm>current reset
IPDU #1: Clearing maximum recorded current to zero.
IPDU #2: Clearing maximum recorded current to zero.
pm>currentprotection status
IPDU #1: Overcurrent protection is OFF.
IPDU #2: Overcurrent protection is OFF.