EasyManua.ls Logo

Danfoss MAGFLO MAG 5000

Danfoss MAGFLO MAG 5000
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
49
MAGFLO
â
7. Electrical connection
Elec.con.
7.2
Wiring diagram for signal
converter and sensor
7.2.1 Integral installation
Integral mount
Remote wall mounting
7.2.2
Remote installation wall
mount NEMA 6 enclosure
Cathodic protected piping
Integral mount installation:
The signal converter must be supplied through an isolation transformer. The terminal "PE" must
not be connected.
Sensor cables
· Unshielded cable ends must be as short as possible and the two cables must be kept separate.
Cables must not be spliced.
· Terminals 81 and 84 are only connected when double shielded is used. See 2.7.1.
· Coil cable shield must be connected at both ends. Electrode cable shields must be connected
at sensor side only.
Note
See 5.3 when using cathodic protection.
Note
Mount a grounding wire to the PE on the connnection board to ensure sufficient grounding.

Table of Contents

Related product manuals