65
MAGFLO
â
8. Start-up & programming
Start-up & programming
8.6.1
Factory settings/available
settings
Parameter Factory settings Available settings
Password
Default value 1000
Password 1000 1000 - 9999
Basic settings
Flow direction Positive Positive, negative
Q
max.
(1+2)
- Volume units Dim. dependent m
3
, ml, l, kl, hl, Ml, ft
3
, in
3
, US G, US kG, US MG, UK G,
UK MG
- Time units Dim. dependent Sec., min., hour, day
Totalizer 1 Forward Forward, reverse, net
- Totalizer 1 units Dim. dependent m
3
, ml, l, kl, hl, Ml, ft
3
, in
3
, US G, US kG, US MG,
UK G, UK MG
Totalizer 2 Reverse Forward, reverse, net
- Totalizer 2 units Dim. dependent m
3
, ml, l, kl, hl, Ml, ft
3
, in
3
, US G, US kG, US MG,
UK G, UK MG
Low flow cut-off 1.5 % 0 - 9.9 %
Empty pipe Off Off, on
Error level Warning Fatal, permanent, warning
Output
Current output Off On/off, uni-/bidirectional, 0/4 - 20 mA
- Direction Uni-directional Uni-/bidirectional
- Function 4-20 mA 0-20 mA, 4-20 mA, 4-20 mA + alarm
- Time constant 5 s 0.1 - 30 s
Digital output Pulse Error, direction/limit, batch
1)
, frequency, pulse, error no.,
off
Relay output Error Error, direction/limit, cleaning, error No., off
Direction/limit switch Off 1 set point/2 set points, - 100 - 100%
- Hysteresis 5% 0.0 - 100%
Batch
1)
Off
- Batch quantity 0 Dim. dependent
- Batch compensation 0 -100 - 100 m
3
- Batch counter Down Up/down
- Time constant 0.1 s 0.1 - 30 s
Frequency Off 500 Hz, 1 kHz, 5 kHz, 10 kHz
- Time constant 5 s 0.1 - 30 s
Pulse On
- Pulse polarity Positive Positive/negative
- Pulse width 66 ms 64 µs, 130 µs, 260 µs, 510 µs, 1.0 ms, 2.0 ms,
4.1 ms, 8.2 ms, 16 ms, 33 ms, 66 ms, 130 ms,
260 ms, 520 ms, 1.0 s, 2.1 s, 4.2 s.
- Volume/pulse Dim. dependent Dim. dependent
- Time constant 0.1 s 0.1 - 30 s
Electrode cleaning Off Off/cleaning
- Cleaning cycle time 24 h 1 - 240 h
External input
External input Off Batch, reset totalizer, freeze output, forced output, off
- Batch Start, hold/continue, stop, Q
max.
2
Sensor characteristics
Correction factor 1 0.85 - 2.00
Language English English, German, French, Danish, Swedish, Finnish,
Spanish, Russian, Italian, Portuguese
Operator menu
Primary field Flow rate Flow rate, Totalizer 1, Totalizer 2
Title/subtitle line Flow rate, Totalizer 1, Flow rate, Flow rate %, Q
max.
, Totalizer 1, Totalizer 2,
totalizer 2, totalizer 1 Totalizer 1 reset, Totalizer 2 reset, Batch start/
reset, totalizer 2 reset, paused/stop, Batch cycle counter, Batch cycle
error pending counter reset, Sensor size, Sensor type, Error
pending, Status log, Tag No.
The signal converter is delivered with factory settings ready to measure the actual flow.
1)
Batch is available on
MAG 6000 only