8-52 DC Brake Select
Option: Function:
NOTICE
Only selection [0] Digital Input is available
when parameter 1-10 Motor Construction is
set to [1] PM, non-salient SPM.
[0] Digital
input
Activates start command via a digital input.
[1] Bus Activates start command via the serial communi-
cation port or eldbus option.
[2] Logic
AND
Activates start command via the eldbus/serial
communication port AND via 1 of the digital
inputs.
[3] Logic OR Activates start command via the eldbus/serial
communication port OR via 1 of the digital inputs.
8-53 Start Select
Select the trigger for the start function.
Option: Function:
[0] Digital input A digital input triggers the start function.
[1] Bus A serial communication port or the eldbus
triggers the start function.
[2] Logic AND The eldbus/serial communication port and a
digital input trigger the start function.
[3] * Logic OR The eldbus/serial communication port or a
digital input triggers the start function.
8-54 Reversing Select
Select control of the frequency converter reverse function via the
terminals (digital input) and/or via the eldbus.
Option: Function:
NOTICE
This parameter is active only when
parameter 8-01 Control Site is set to [0]
Digital and control word.
[0] * Digital input Activates reverse command via a digital input.
[1] Bus Activates reverse command via the serial
communication port or eldbus option.
[2] Logic AND Activates reverse command via the eldbus/
serial communication port and via 1 of the
digital inputs.
[3] Logic OR Activates reverse command via the eldbus/
serial communication port or via 1 of the
digital inputs.
Parameter Description