14-10 Mains Failure
Option: Function:
Ref
U
DC
14-15
A B C D EA
130BC922.10
U
DC
[V]
n [RPM]
t [S]
t [S]
14-11*1.35
A Normal operation.
B Mains failure.
C Kinetic back-up.
D Mains return.
E Normal operation: ramping.
Illustration 3.47 Kinetic Back-Up, Trip with
Recovery where Mains Return above
Parameter 14-15 Kin. Back-up Trip Recovery
Level
If mains return while in kinetic back-up at a speed
below parameter 14-15 Kin. Back-up Trip Recovery
Level, the frequency converter ramps down to 0
RPM using the ramp and then trips. If the ramp is
slower than the system ramping down on its own,
the ramping is done mechanically and U
DC
is at
the normal level (U
DC, m
x 1.35).
14-11*1.35
Ref
U
DC
A B C D E F
130BC923.10
0
U
DC
[V]
n [RPM]
t [S]
t [S]
A Normal operation.
B Mains failure.
C Kinetic back-up.
D Mains return.
E Kinetic back-up, ramping to trip.
F Trip.
Illustration 3.48 Kinetic Back-Up, Trip with
Recovery, Trip Slow Ramp where Mains Return
below Parameter 14-15 Kin. Back-up Trip
Recovery Level, here a Slow Ramp is Used
If the ramp is quicker than the ramp-down speed
of the application, the ramping generates current.
This results in a higher U
DC
, which is limited using
the brake chopper/resistor brake.
14-10 Mains Failure
Option: Function:
14-11*1.35
U
DC
0
U
DC
Ref
A B C D E F
130BC924.10
U
n [RPM]
t [s]
DC
[V]
t [s]
A Normal operation.
B Mains failure.
C Kinetic back-up.
D Mains return.
E Kinetic back-up ramping to trip.
F Trip.
Illustration 3.49 Kinetic Back-Up, Trip with
Recovery where Mains Return below
Parameter 14-15 Kin. Back-up Trip Recovery
Level, here a Quick Ramp is Used
NOTICE
For best performance of controlled ramp down and
kinetic back-up, set parameter 1-03 Torque Characteristics
to [0] Compressor or [1] Variable Torque (no automatic
energy optimization should be active).
DC Voltage
Output Speed rpm
Over Voltage Control Level
Mains
Time
130BT101.10
Par 14-11
Illustration 3.50 Controlled Ramp Down, Short Mains Failure.
Illustration 3.50 shows ramping down to a stop followed by
ramping up to the reference.
Mains
Time
DC Voltage
Output Speed rpm
Over Voltage Control Level
130BT108.10
Par 14-11
Illustration 3.51 Controlled Ramp Down, Longer Mains Failure.
Illustration 3.51 shows ramping down as long as the energy
in the system allows it, then the motor coasts.
Parameter Description
VLT
®
AQUA Drive FC 202
134 Danfoss A/S © 05/2018 All rights reserved. MG20OB02
33

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals