EasyManuals Logo

Danfoss VLT AQUA Drive FC 202 Programming Guide

Danfoss VLT AQUA Drive FC 202
294 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #189 background imageLoading...
Page #189 background image
22-61 Broken Belt Torque
Range: Function:
10 %* [0 - 100 %] Sets the broken-belt torque as a percentage
of the rated motor torque.
22-62 Broken Belt Delay
Range: Function:
10 s [0 - 600
s]
Sets the time for which the broken belt
conditions must be active before carrying out
the action selected in parameter 22-60 Broken
Belt Function.
3.19.7 22-7* Short Cycle Protection
In some applications, a need for limiting the numbers of
starts often exists. One way to do this is to ensure a
minimum run time (time between a start and a stop) and a
minimum interval between starts.
This means that any normal stop command can be
overridden by parameter 22-77 Minimum Run Time and any
normal start command (start/jog/freeze) can be overridden
by parameter 22-76 Interval between Starts.
None of the 2 functions are active if hand-on mode or
o
mode have been activated via the LCP. If pressing [Hand
On] or [O], the 2 timers are reset to 0 and do not start
counting until [Auto On] is pressed, and an active start
command is applied.
22-75 Short Cycle Protection
Option: Function:
[0] * Disabled Timer set in parameter 22-76 Interval between
Starts is disabled.
[1] Enabled Timer set in parameter 22-76 Interval between
Starts is enabled.
22-76 Interval between Starts
Range: Function:
Size related* [ par. 22-77 -
3600 s]
Sets the minimum time between 2
starts. Any normal start command
(start/jog/freeze) is disregarded
until the timer has expired.
22-77 Minimum Run Time
Range: Function:
0 s* [ 0 - par.
22-76 s]
NOTICE
Does not work in cascade mode.
Sets the minimum run time after a normal start
command (start/jog/freeze). Any normal stop
command is disregarded until the set time has
22-77 Minimum Run Time
Range: Function:
expired. The timer starts counting following a
normal start command (start/jog/freeze).
A coast (inverse) or an external interlock
command overrides the timer.
22-78 Minimum Run Time Override
Option: Function:
[0] * Disabled
[1] Enabled
22-79 Minimum Run Time Override Value
Range: Function:
0 ProcessCtrlUnit* [-999999.999 - 999999.999
ProcessCtrlUnit]
3.19.8 22-8* Flow Compensation
In certain applications, it is not possible for a pressure
transducer to be placed at a remote point in the system,
and it can only be located close to the fan/pump outlet.
Flow compensation operates by adjusting the setpoint
according to the output frequency, which is almost propor-
tional to ow. Thus, it compensates for higher losses at
higher ow rates.
H
DESIGN
(required pressure) is the setpoint for closed-loop
(PI) operation of the frequency converter and is set as for
closed-loop operation without ow compensation.
130BA383.11
Illustration 3.70 Flow Compensation Set-up
There are 2 methods which can be employed, depending
on whether the speed at system design working point is
known.
Parameter Description Programming Guide
MG20OB02 Danfoss A/S © 05/2018 All rights reserved. 187
3 3

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals