Parameter used
Speed at design point
known
Speed at design point
unknown
Parameter 22-80 Flow Compensation + +
Parameter 22-81 Square-linear Curve Approximation + +
Parameter 22-82 Work Point Calculation + +
Parameter 22-83 Speed at No-Flow [RPM]/parameter 22-84 Speed at No-
Flow [Hz]
+ +
Parameter 22-85 Speed at Design Point [RPM]/parameter 22-86 Speed at
Design Point [Hz]
+ –
Parameter 22-87 Pressure at No-Flow Speed + +
Parameter 22-88 Pressure at Rated Speed – +
Parameter 22-89 Flow at Design Point – +
Parameter 22-90 Flow at Rated Speed – +
Table 3.30 Speed at Design Point Known/Unknown
22-80 Flow Compensation
Option: Function:
[0] * Disabled Setpoint compensation not active.
[1] Enabled Setpoint compensation is active. Enabling this
parameter allows the ow-compensated setpoint
operation.
22-81 Square-linear Curve Approximation
Range: Function:
100 %* [0 - 100 %]
NOTICE
Not visible when running in cascade.
Example 1
Adjustment of this parameter allows the
shape of the control curve to be adjusted.
0=Linear
100%=Ideal shape (theoretical).
Control Curve
(head)
(ow)
H
Q
130BA388.11
100%
P22-81 0%
Illustration 3.71 Square-Linear Curve Approximation
22-82 Work Point Calculation
Option: Function:
Example 1
A
130BA385.11
P22-85/22-86
Control Curve
H
MIN
H
DESIGN
Set Point
n
RATED
_
f
RATED
n
DESIGN
-
f
DESIGN
Q
(flow)
H
(head)
Par.:
22-83/
22-84/
22-87
Illustration 3.72 Speed at System Design
Working Point is Known
From the datasheet showing characteristics for the
specic equipment at dierent speeds, simply
reading across from the H
DESIGN
point and the
Q
DESIGN
point allows nding point A, which is the
system design working point. The pump character-
istics at this point should be identied and the
associated speed programmed. Closing the valves
and adjusting the speed until H
MIN
has been
achieved allows the speed at the no-ow point to
be identied.
Adjustment of parameter 22-81 Square-linear Curve
Approximation then allows the shape of the
control curve to be adjusted innitely.
Example 2
Speed at system design working point is not
known: Where the speed at system design
working point is unknown, another reference point
on the control curve has to be determined based
on the datasheet. Looking at the curve for the
rated speed and plotting the design pressure
(H
DESIGN
, Point C), the ow at that pressure, Q
RATED
,
can be determined. Similarly, by plotting the
design ow (Q
DESIGN
, Point D), the pressure H
DESIGN
Parameter Description
VLT
®
AQUA Drive FC 202
188 Danfoss A/S © 05/2018 All rights reserved. MG20OB02
33