3.25.5 29-5* Flow Conrmation
The ow conrmation feature is designed for applications
where there is a need for the motor/pump to run while
waiting for an external event. The ow conrmation
monitor expects to receive a digital input from a sensor on
a gate valve, ow switch, or a similar external device,
indicating that the device is in the open position and ow
is possible. In parameter 29-50 Validation Time, dene for
how long the VLT
®
AQUA Drive FC 202 waits for the digital
input signal from the external device to conrm the ow.
After the ow is conrmed, the frequency converter checks
the signal again after the ow verication time and then
runs normally. The LCP status reads Verifying ow while the
ow monitor is active.
The frequency converter trips with the alarm Flow Not
Conrmed if the expected digital input signal becomes
inactive before either the ow validation time or the ow
verication time expires.
130BD766.10
N
MAX
N
MIN
0
0
1
1
0
1
0
1
2
3
4
t0 <t1 t2
T
T
T
T
1 Speed curve.
2 Start command (for example, terminal 18).
3 Digital signal from an external device that conrms that
the ow is possible.
4 Flow verication.
t
0
Start command issued (for example, terminal 18 is set
active).
t
1
Digital signal from an external device becomes active
before parameter 29-50 Validation Time expires.
t
2
When parameter 29-51 Verication Time passes, the
frequency converter checks the signal from the external
device again and then runs normally.
Illustration 3.115 Flow Conrmation
29-50 Validation Time
Range: Function:
Size
related*
[ 0 -
999 s]
NOTICE
Parameter 29-50 Validation Time is
only visible in the LCP if a digital
input is set to [86] Flow Conrmation
(see parameter group 5-1* Digital
Inputs).
The digital input from an external device
must be active during the validation time.
29-51 Verication Time
Range: Function:
15 s* [ 0.10 -
255 s]
NOTICE
Parameter 29-51 Verication Time is only
visible in the LCP if a digital input is set
to [86] Flow Conrmation (see parameter
group 5-1* Digital Inputs).
When the time in this parameter passes, the
frequency converter checks the signal from the
external device. If the signal is active, the
frequency converter runs normally.
29-52 Signal Lost Verication Time
Enter the length of the delay after which the signal is considered
to be lost. This parameter is ignored if parameter 29-53 Flow
Conrmation Mode is set to [0] Conrmation Only.
Range: Function:
1 s* [0.01 - 255 s]
29-53 Flow Conrmation Mode
Select the operating mode of the ow monitor function.
Option: Function:
[0] * Conrmation
Only
The ow conrmation function is only
active during the start-up of the pump.
[1] Monitor and
Stop
The ow conrmation function is active
during and after the pump start-up. The
frequency converter performs a ramp
down to a stop if the input signal is lost.
[2] Monitor and
Coast
The ow conrmation function is active
during and after the pump start-up. The
frequency converter performs coasting if
the input signal is lost.
Parameter Description
VLT
®
AQUA Drive FC 202
240 Danfoss A/S © 05/2018 All rights reserved. MG20OB02
33

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals