EasyManuals Logo

Danfoss VLT AQUA Drive FC 202 Programming Guide

Danfoss VLT AQUA Drive FC 202
294 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #39 background imageLoading...
Page #39 background image
3.2.7 0-6* Password
0-60 Main Menu Password
Range: Function:
100* [-9999 -
9999 ]
Dene the password for access to the Main
Menu via the [Main Menu] key. If
parameter 0-61 Access to Main Menu w/o
Password is set to [0] Full access, this
parameter is ignored.
0-61 Access to Main Menu w/o Password
Option: Function:
[0] * Full access Disables the password dened in
parameter 0-60 Main Menu Password. If this
option is selected, parameter 0-60 Main Menu
Password, parameter 0-65 Personal Menu
Password, and parameter 0-66 Access to
Personal Menu w/o Password are ignored.
[1] LCP: Read
only
Prevents unauthorized editing of Main Menu
parameters.
[2] LCP: No
access
Prevents unauthorized viewing and editing of
Main Menu parameters.
[3] Bus: Read
only
Provides read-only access to parameters via
eldbus.
[4] Bus: No
access
Disables access to parameters via eldbus.
[5] All: Read
only
Prevents unauthorized editing of Main Menu
parameters and provides read-only access to
parameters via eldbus.
[6] All: No
access
Prevents unauthorized viewing and editing of
Main Menu parameters and disables access to
parameters via eldbus.
0-65 Personal Menu Password
Range: Function:
200* [-9999 -
9999 ]
Dene the password for access to My Personal
Menu via the [Quick Menu] key. If
parameter 0-66 Access to Personal Menu w/o
Password is set to [0] Full access, this
parameter is ignored.
0-66 Access to Personal Menu w/o Password
If parameter 0-61 Access to Main Menu w/o Password is set to [0]
Full access, this parameter is ignored.
Option: Function:
[0] * Full access Disables the password dened in
parameter 0-65 Personal Menu Password.
[1] LCP: Read only Prevents unauthorized editing of My
Personal Menu parameters.
[3] Bus: Read only
[5] All: Read only
0-67 Bus Password Access
Range: Function:
0 N/A* [0 - 9999 N/A] Writing to this parameter enables
unlocking of the frequency converter
from bus/MCT 10 Set-up Software.
3.2.8 0-7* Clock Settings
Set the time and date of the internal clock. For example,
the internal clock can be used for:
Timed actions.
Energy log.
Trend analysis.
Date/time stamps on alarms.
Logged data.
Preventive maintenance.
It is possible to program the clock for daylight saving time/
summer time, weekly working days/non-working days,
including 20 exceptions (holidays, and so on). Although the
clock settings can be set via the LCP, they can also be set
along with timed actions and preventive maintenance
functions using the MCT 10 Set-up Software tool.
NOTICE
The frequency converter has no back-up of the clock
function and the set date/time resets to default
(01.01.2007 00:00 Mon) after a power-down, unless a
real-time clock-module with back-up is installed. If no
module with back-up is installed, only use the clock
function if the frequency converter is integrated into an
external system using serial communication, with the
system maintaining synchronization of control
equipment clock times. In parameter 0-79 Clock Fault, it is
possible to program a warning if the clock has not been
set properly, for example, after a power-down.
NOTICE
When mounting VLT
®
Analog I/O Option MCB 109 or
VLT
®
Real-time Clock MCB 117, a battery back-up of the
date and time is included.
0-70 Date and Time
Range: Function:
Size
related*
[ 0 -
0 ]
Sets the date and time of the internal clock.
The format to be used is set in
parameter 0-71 Date Format and
parameter 0-72 Time Format.
When using VLT
®
Real-time Clock MCB 117,
the time is synchronized at 15:00 every day.
Parameter Description Programming Guide
MG20OB02 Danfoss A/S © 05/2018 All rights reserved. 37
3 3

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals