0-71 Date Format
Option: Function:
[0] YYYY-MM-DD Sets the date format to be used in the LCP.
[1] DD-MM-YYYY Sets the date format to be used in the LCP.
[2] MM/DD/YYYY Sets the date format to be used in the LCP.
0-72 Time Format
Option: Function:
Sets the time format to be used in the LCP.
[0] 24 h
[1] 12 h
0-73 Time Zone Oset
Range: Function:
0 min* [-780 - 780
min]
Enter the time zone oset relative to
UTC. This parameter is required for the
automatic daylight saving time
adjustment.
0-74 DST/Summertime
Option: Function:
Select how to handle daylight saving time/summer
time. For manual setting of DST/summer time,
enter the start date and end date in
parameter 0-76 DST/Summertime Start and
parameter 0-77 DST/Summertime End.
[0] * O
[2] Manual
0-76 DST/Summertime Start
Range: Function:
Size
related*
[ 0 - 0 ] Sets the date and time when DST/
summer time starts. The date is
programmed in the format selected in
parameter 0-71 Date Format.
0-77 DST/Summertime End
Range: Function:
Size
related*
[ 0 - 0 ] Sets the date and time when DST/
summer time ends. The date is
programmed in the format selected in
parameter 0-71 Date Format.
0-79 Clock Fault
Option: Function:
Enables or disables the clock warning when the
clock has not been set, or has been reset due to a
power-down and no back-up is installed. If VLT
®
Analog I/O Option MCB 109 is installed, [1] Enabled
is default.
[0] Disabled
[1] Enabled
0-81 Working Days
Array [7]
Array with 7 elements [0]–[6] shown below the parameter
number in the display. Press [OK] and step between elements
with [
▲
] and [
▼
].
Option: Function:
Set for each weekday if it is a working day or a non-
working day. First element of the array is Monday. The
working days are used for timed actions.
[0] No
[1] Yes
0-82 Additional Working Days
Array [5]
Array with 5 elements [0]–[4] shown below the parameter
number in the display. Press [OK] and step between elements
with [
▲
] and [
▼
].
Range: Function:
Size related* [ 0 - 0 ] Denes dates for additional working days
that would normally be non-working
days according to parameter 0-81 Working
Days.
0-83 Additional Non-Working Days
Array [15]
Array with 15 elements [0]–[14] shown below the parameter
number in the display. Press [OK] and step between elements
with [
▲
] and [
▼
].
Range: Function:
Size related* [ 0 - 0 ] Denes dates for additional working days
that would normally be non-working
days according to parameter 0-81 Working
Days.
0-84 Time for Fieldbus
Range: Function:
0* [0 - 4294967295 ] Shows the time for eldbus.
0-85 Summer Time Start for Fieldbus
Range: Function:
0* [0 - 4294967295 ] Shows the summer time start for
eldbus.
0-86 Summer Time End for Fieldbus
Range: Function:
0* [0 - 4294967295 ] Shows the summer time end for eldbus.