0-71 Date Format
Option: Function:
[0] YYYY-MM-DD Sets the date format to be used in the LCP.
[1] DD-MM-YYYY Sets the date format to be used in the LCP.
[2] MM/DD/YYYY Sets the date format to be used in the LCP.
0-72 Time Format
Option: Function:
Sets the time format to be used in the LCP.
[0] 24 h
[1] 12 h
0-73 Time Zone Oset
Range: Function:
0 min* [-780 - 780
min]
Enter the time zone oset relative to
UTC. This parameter is required for the
automatic daylight saving time
adjustment.
0-74 DST/Summertime
Option: Function:
Select how to handle daylight saving time/summer
time. For manual setting of DST/summer time,
enter the start date and end date in
parameter 0-76 DST/Summertime Start and
parameter 0-77 DST/Summertime End.
[0] * O
[2] Manual
0-76 DST/Summertime Start
Range: Function:
Size
related*
[ 0 - 0 ] Sets the date and time when DST/
summer time starts. The date is
programmed in the format selected in
parameter 0-71 Date Format.
0-77 DST/Summertime End
Range: Function:
Size
related*
[ 0 - 0 ] Sets the date and time when DST/
summer time ends. The date is
programmed in the format selected in
parameter 0-71 Date Format.
0-79 Clock Fault
Option: Function:
Enables or disables the clock warning when the
clock has not been set, or has been reset due to a
power-down and no back-up is installed. If VLT
®
Analog I/O Option MCB 109 is installed, [1] Enabled
is default.
[0] Disabled
[1] Enabled
0-81 Working Days
Array [7]
Array with 7 elements [0]–[6] shown below the parameter
number in the display. Press [OK] and step between elements
with [
] and [
].
Option: Function:
Set for each weekday if it is a working day or a non-
working day. First element of the array is Monday. The
working days are used for timed actions.
[0] No
[1] Yes
0-82 Additional Working Days
Array [5]
Array with 5 elements [0]–[4] shown below the parameter
number in the display. Press [OK] and step between elements
with [
] and [
].
Range: Function:
Size related* [ 0 - 0 ] Denes dates for additional working days
that would normally be non-working
days according to parameter 0-81 Working
Days.
0-83 Additional Non-Working Days
Array [15]
Array with 15 elements [0]–[14] shown below the parameter
number in the display. Press [OK] and step between elements
with [
] and [
].
Range: Function:
Size related* [ 0 - 0 ] Denes dates for additional working days
that would normally be non-working
days according to parameter 0-81 Working
Days.
0-84 Time for Fieldbus
Range: Function:
0* [0 - 4294967295 ] Shows the time for eldbus.
0-85 Summer Time Start for Fieldbus
Range: Function:
0* [0 - 4294967295 ] Shows the summer time start for
eldbus.
0-86 Summer Time End for Fieldbus
Range: Function:
0* [0 - 4294967295 ] Shows the summer time end for eldbus.
Parameter Description
VLT
®
AQUA Drive FC 202
38 Danfoss A/S © 05/2018 All rights reserved. MG20OB02
33

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals