EasyManuals Logo

Danfoss VLT AQUA Drive FC 202 Programming Guide

Danfoss VLT AQUA Drive FC 202
294 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #80 background imageLoading...
Page #80 background image
[19] Freeze ref Freezes the actual reference. The frozen
reference is now the point of enable/
condition for speed up and speed down to
be used. If speed up/speed down is used,
the speed change always follows ramp 2
(parameter 3-51 Ramp 2 Ramp Up Time and
parameter 3-52 Ramp 2 Ramp Down Time) in
the range 0–parameter 3-03 Maximum
Reference.
[20] Freeze output Freezes the actual motor frequency (Hz). The
frozen motor frequency is now the point of
enable/condition for speed up and speed
down to be used. If speed up/speed down is
used, the speed change always follows ramp
2 (parameter 3-51 Ramp 2 Ramp Up Time and
parameter 3-52 Ramp 2 Ramp Down Time) in
the range 0–parameter 1-23 Motor Frequency.
NOTICE
When [20] Freeze output is active, the
frequency converter cannot be
stopped via a low [13] Start signal.
Stop the frequency converter via a
terminal programmed for [2] Coast
inverse or [3] Coast and reset, inverse.
[21] Speed up For digital control of the speed up/speed
down (motor potentiometer). Activate this
function by selecting either [19] Freeze
reference or [20] Freeze output. When [21]
Speed up is activated for less than 400 ms,
the resulting reference is increased by 0.1%.
If [21] Speed up is activated for more than
400 ms, the resulting reference ramps
according to ramp 1 in parameter 3-41 Ramp
1 Ramp Up Time.
[22] Speed down Same as [21] Speed up.
[23] Set-up select
bit 0
Selects 1 of the 4 set-ups. Set
parameter 0-10 Active Set-up to Multi Set-up.
[24] Set-up select
bit 1
Same as [23] Set-up select bit 0.
(Default digital input 32).
[32] Pulse input Select [32] Pulse input when using a pulse
sequence as either reference or feedback.
Scaling is done in parameter group 5-5* Pulse
Input.
[34] Ramp bit 0 Select which ramp to use. Logic 0 selects
ramp 1 while logic 1 selects ramp 2.
[36] Mains failure
inverse
Activates parameter 14-10 Mains Failure.
Mains failure inverse is active in the logic 0
situation.
[42] Ref source bit
0
An active input in bit 0 selects AI54 as the
reference source (see parameter group 3-1*
References, option [35] Digital input select).
An inactive input selects AI53.
[51] Hand/Auto
Start
Selects hand or auto start. High signal
selects auto on only, Low signal selects hand
on only.
[52] Run
Permissive
The input terminal, for which the [52] Run
Permissive has been programmed, must be
logic 1 before a start command can be
accepted. Run permissive has a logic AND
function related to the terminal, which is
programmed for [8] Start, [14] Jog, or [20]
Freeze Output. To start running the motor,
both conditions must be fullled. If [52] Run
Permissive is programmed on multiple
terminals, it only has to be logic 1 on 1 of
the terminals to carry out the function. The
digital output signal for run request ([8]
Start, [14] Jog, or [20] Freeze output)
programmed in parameter group 5-3* Digital
Outputs, or parameter group 5-4* Relays, is
not aected by [52] Run Permissive.
[53] Hand start A signal applied puts the frequency
converter into hand-on mode as if [Hand
On] has been pressed and a normal stop
command is overridden. If disconnecting the
signal, the motor stops. To make any other
start commands valid, assign another digital
input to [54] Auto Start and apply a signal to
this. [Hand On] and [Auto On] have no
impact. [O] overrides local start and auto
start. Press either [Hand On] or [Auto On] to
make local start and auto start active again.
If there is no signal on neither [53] Hand
start nor [54] Auto start, the motor stops
regardless of any normal start command
applied. If a signal is applied to both [53]
Hand start and [54] Auto start, the function is
auto start. If pressing [O], the motor stops
regardless of signals on [53] Hand start and
[54] Auto start.
[54] Auto start A signal applied puts the frequency
converter into auto-on mode as if [Auto On]
has been pressed. See also [53] Hand Start.
[55] DigiPot
Increase
Uses the input as an increase signal to the
digital potentiometer function described in
parameter group 3-9* Digital Pot.Meter.
[56] DigiPot
Decrease
Uses the input as a decrease signal to the
digital potentiometer function described in
parameter group 3-9* Digital Pot.Meter.
[57] DigiPot Clear Uses the input to clear the digital potenti-
ometer reference described in parameter
group 3-9* Digital Pot.Meter.
[60] Counter A
(up)
(Terminal 29 or 33 only) Input for increment
counting in the SLC counter.
[61] Counter A
(down)
(Terminal 29 or 33 only) Input for decrement
counting in the SLC counter.
[62] Reset Counter
A
Input for reset of counter A.
[63] Counter B
(up)
(Terminal 29 and 33 only) Input for
increment counting in the SLC counter.
[64] Counter B
(down)
(Terminal 29 and 33 only) Input for
decrement counting in the SLC counter.
Parameter Description
VLT
®
AQUA Drive FC 202
78 Danfoss A/S © 05/2018 All rights reserved. MG20OB02
33

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals