EasyManua.ls Logo

Dell PowerEdge R960 - Environmental Specifications

Dell PowerEdge R960
227 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 18. Video specifications for R960
Resolution Refresh rate
(Hz)
Sestotal Freq. Pixel Clock DVO DisplayPort
1024 x 768 60 Hz 48.4 kHz 65.0 MHz Yes*
1280 x 800 60 Hz 49.7 kHz 83.5 MHz Yes*
1280 x 1024 60 Hz 64.0 kHz 108.0 MHz Yes*
1360 x 768 60 Hz 47.71 kHz 85.5 MHz Yes*
1440 x 900 60 Hz 55.9 kHz 106.5 MHz Yes*
1600 x 900 60 Hz 55.54 kHz 97.75 MHz Yes*
1600 x 1200 60 Hz 75.0 kHz 162.0 MHz Yes*
1680 x 1050 60 Hz 64.7 kHz 119.0 MHz Yes*
1920 x 1080 60 Hz (RB)^ 67.158 kHz 173.0 MHz No
1920 x 1200 60 Hz (RB) ^ 74.556 kHz 193.25 MHz No
*DVO - DP is for investigation only, dependent on Nuvoton DVO capabilities to support up to 165 MHz.
^(RB) - Reduced Blanking for Digital Displays requiring less blank time. It was introduced for Signal Integrity improvements by
reducing Pixel Clock rates for VGA- Analog input devices.
Environmental specifications
NOTE:
For additional information about environmental certifications, refer to the Product Environmental Datasheet located
with the Documentation on www.dell.com/support/home.
Table 19. Continuous Operation Specifications for ASHRAE A2
Temperature Specifications
Allowable continuous operations
Temperature range for
altitudes < 900 m (< 2953
ft)
1035°C (5095°F) with no direct sunlight on the equipment
Humidity percent range
(non-condensing at all
times)
8% RH with -12°C (10.4°F) minimum dew point to 80% RH with 21°C (69.8°F) maximum dew
point
Operational altitude de-
rating
Maximum temperature is reduced by 1°C/300 m (1.8°F/984 Ft) above 900 m (2953 Ft)
Table 20. Continuous Operation Specifications for ASHRAE A3
Temperature Specifications
Allowable continuous operations
Temperature range for
altitudes <= 900 m (<=
2953 ft)
540°C (41104°F) with no direct sunlight on the equipment
Humidity percent range
(non-condensing at all
times)
8% RH with -12°C (10.4°F) minimum dew point to 85% RH with 24°C (75.2°F) maximum dew
point
Operational altitude de-
rating
Maximum temperature is reduced by 1°C/175 m (1.8°F/574 Ft) above 900 m (2953 Ft)