NOTE: Shared management of iDRAC is capable through the embedded LOM and OCP ports.
Video specifications
The PowerEdge XR5610 system supports integrated Matrox G200 graphics controller with 16 MB of video frame buffer.
Table 24. Supported video resolution options for the system
Resolution Refresh Rate Color depth (Bits)
1024 x 768 60 Hz 8, 16, 32
1280 x 800 60 Hz 8, 16, 32
1280 x 1024 60 Hz 8, 16, 32
1360 x 768 60 Hz 8, 16, 32
1440 x 900 60 Hz 8, 16, 32
1600 x 900 60 Hz 8, 16, 32
1600 x 1200 60 Hz 8, 16, 32
1680 x 1050 60 Hz 8, 16, 32
1920 x 1080 60 Hz (RB) 8, 16, 32
1920 x 1200 60 Hz (RB) 8, 16, 32
Environmental specifications
The PowerEdge XR5610 system operates in these environmental categories: ASHRAE A2/A3/A4 and Edge1 (50°C) and Edge2
(55°C).
NOTE:
For additional information about environmental certifications, refer to the Product Environmental Datasheet located
with the Documentation > Regulatory Information on www.dell.com/support/home.
Table 25. Continuous operation specifications for ASHRAE A2
Feature Allowable continuous operations
Temperature range for altitudes <= 900 m (<=
2953 ft)
10–35°C (50–95°F) with no direct sunlight on the equipment
Humidity percent range (non-condensing at all
times)
8% RH with -12°C minimum dew point to 80% RH with 21°C (69.8°F)
maximum dew point
Operational altitude de-rating Maximum temperature is reduced by 1°C/300 m (33.8°F/984 Ft) above
900 m (2953 Ft)
Table 26. Continuous operation specifications for ASHRAE A3
Feature Allowable continuous operations
Temperature range for altitudes <= 900 m (<=
2953 ft)
5–40°C (41–104°F) with no direct sunlight on the equipment
Humidity percent range (non-condensing at all
times)
8% RH with -12°C minimum dew point to 85% RH with 24°C (75.2°F)
maximum dew point
Operational altitude de-rating Maximum temperature is reduced by 1°C/175 m (33.8°F/574 Ft) above
900 m (2953 Ft)
Technical specifications 37