Chapter 7 Servo Parameters  ASDA-B2 
7-26  Revision September 2013 
Speed limit setting is as the following: 
P1-09(1)
P1-10(2)
P1-11(3)
Vref
SPD0
SPD1
(0)
Speed Limit
Command
 
Users could use speed limit function via parameter setting or DI triggering. That is to 
say, set P1-02 to 0x0001 or trigger DI will do. Also, users could enable or disable the 
limit function via DI. SPDLM, which is a more flexible way but would need to take one 
DI setting. Speed limit can be enabled by P1-02 or DI.   
DI.SPD0 and DI.SPD1 are for selecting the limiting source. 
 
  Disable or Enable torque limit function 
0: Disable torque limit function 
1: Enable torque limit function (It is available in position and speed mode) 
Other: Reserved 
P1-12(1)
P1-13(2)
P1-14(3)
Tref
TCM0
TCM1
(0)
Torque Limit
Command
 
Users could use torque limit function via parameter setting or DI triggering. That is to 
say, set P1-02 to 0x0010 or trigger DI will do. Also, users could enable or disable the 
limit function via DI.TRQLM, which is a more flexible way but would need to take one 
DI setting. Torque limit can be enabled by P1-02 or DI.   
DI.TCM0 and DI.TCM1 are for selecting the limiting source. 
 
P1-03    AOUT  Pulse Output Polarity Setting   
Address: 0106H 
0107H 
 
Operation 
Interface: 
Keypad/Software   Communication  
Related Section: 
Section 3.3.3 
 
Default: 0 
 
Control 
Mode: 
ALL 
 
Unit: - 
 
Range: 0 ~ 13 
 
Data Size: 16-bit 
 
Display 
Format: 
Hexadecimal 
Settings: 