51ECL-PTU-207 Preloaded Applications
3. Double-click the BcpLonNetwork driver. The Bcp Lon Device Manager appears in the View pane.
4. Click Discover. The discovered devices appear in the View pane’s top section and the BcpLon-
Network database appears in the bottom section.
5. Select the discovered device that is to be matched with the one just added to the database. Click
Match.
Figure14: Matching discovered device with Device in Database
The
Match
window appears.
Figure15: Match Window
Using the dcgfxApplications