EasyManua.ls Logo

Eaton DS7 - Page 201

Eaton DS7
240 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 SmartWire-DT
8.9 Programming
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com 197
8.9.5.4 Acyclic PKE motor-protective circuit-breaker data
In addition to cyclic input and output bytes, the DS7-SWD soft starter makes
it possible to read the following acyclic PKE data. The parameter channel
described in the following section is not required for transmitting the data.
Table 40: Available data
Index
Byte Bit Designation Description
1 0 0 - 7 I_REL Relative motor current PKE :
Set rated operational current on PKE
00
hex –
FF
hex
(i. e. 0 - 255 %)
2 0 0 - 7 TH PKE thermal motor map (specified as a percentage)
3 0 0 - 2 TYPE Part no. of PKE trip block
Value [hex] PKE- trip block
0 XTUA-1.2 0.3 - 1.2 A
1 XTUA-4 1.0 - 4.0 A
2 XTUA-12 3.0 - 12 A
3 XTUA-32 8.0 - 32 A
4 XTUWA-32 8.0 – 32 A
(width 55 mm)
5 XTUWA-65 16.0 - 65 A
3 - 5 CLASS set PKE time lag
Value [hex] Time-lag class Time
0 Class 5 146.2 s
1 Class 10 292.5 s
2 Class 15 438.7 s
3 Class 20 585.0 s
4 test
6, 7 Not used
For a description of acyclic communications with the PKE
motor-protective circuit-breaker via PROFIBUS-DP, see
section 8.9.9, “Acyclic data via PROFIBUS-DP: PKE”.

Table of Contents