8 SmartWire-DT
8.9 Programming
DS7 Soft starter 09/16 MN03901001Z-EN www.eaton.com 209
8.9.8.4 SmartWire-DT write response(-) – Error
This section shows the various possible device-specific errors that can occur
during
communications
via
the
acyclic
parameter channel
with
PROFIBUS-DP.
The following table describes the various possible errors that can be
contained in the SmartWire-DT write response(-) – error.
In the case of XSoft-CoDeSys, only error code 54
dec
(representing the errors
listed above) can be output via function blocks XDPMV1_READ and
XDPMV1_WRITE when using a PROFIBUS-DP master.
8.9.8.5 SmartWire-DT read response(-) – Error
This section shows the various possible device-specific errors that can occur
during
communications
via
the
acyclic
parameter channel
with
PROFIBUS-DP.
The following table describes the various possible errors that can be
contained in the SmartWire-DT read response(-) – error.
In the case of XSoft-CoDeSys, only error code 54dec (representing the errors
listed above) can be output via function blocks XDPMV1_READ and
XDPMV1_WRITE when using a PROFIBUS-DP master.
Error Type Failure code Description
Error_Code_1 A1
hex
Write error: Only reading allowed for indexes 1 – 3 (PKE motor-protective
circuit-breaker).
Error_Code_1
A2
hex
DS7-SWD soft starter cannot be reached.
Error_Code_1 B0
hex
There is no valid index.
Error_Code_1 B1
hex
Parameter request block too long.
Error_Code_1
B5
hex
Parameter access temporarily not permissible due to internal processes.
For more information, see section 8.9.6, “Acyclic parameter
channel for DS7-SWD soft starter”, page 198.
Error Type Failure code Description
Error_Code_1 A1
hex
Write error: Only reading allowed for indexes 1 – 3
(PKE motor-protective circuit-breaker).
Error_Code_1
A2
hex
DS7-SWD soft starter cannot be reached.
Error_Code_1
B0
hex
There is no valid index.
Error_Code_1
B5
hex
Parameter access temporarily not permissible due to internal processes
For more information, see section 8.9.6, “Acyclic parameter
channel for DS7-SWD soft starter”, page 198.
For more information on the subject of acyclic data access
blocks for PROFIBUS-DP, consult manual MN05010002Z-EN,
“Function Blocks for XSoft-CoDeSys.”