8.3 Mounting
Standard RTK 725B units are designed for panel mounting, as an option they can be supplied
fitted within 19” filler plates to allow direct mounting into Industry standard 19” rack systems or
fully integrated into wall or floor standing panels.
8.4 Panel Mouting
WARNING !
This annunciator is designed for panel mounting. The rear portion of the
annunciator must be protected by an enclosure that is at least IP30 and can
only be accessed using a key or tool. Access to the rear enclosure must be
limited to service personnel only.
CABINET DIMENSIONS IN MM
WIDE HIGH
Cells Overall Cut-Out Cells Overall Cut-Out
1 88 74 1 88 74
2 148 134 2 148 134
3 208 194 3 208 194
4 268 254 4 268 254
5 328 314 5 328 314
6 388 374 6 388 374
7 448 434 7 448 434
8 508 494 8 508 494
9 568 554 9 568 554
10 628 614 10 628 614
11 688 674 11 688 674
12 748 734 12 748 734
13 808 794 13 808 794
14 868 854 14 868 854
15 928 914 15 928 914
16 988 974 16 988 974
NOTE:
The cut out tolerance should be with ±2mm.r.
Annunciator depth is 143mm
CAUTION
The above table indicates the dimensions based on the number of cells high and wide
this should not be confused with the number of alarm windows.
The number of windows available per cell is determined by the window style