46 Chapter 6 Parameter Descriptions
0
K
1
K
2
0
1
0
0
1
1
1
operation
command
run forward
run reverse
stop
K
1
K
2
OD
COM
CD
TD3200
drive
.
.
.
.
run forward
Figure 6-2 Terminal control mode of general-purpose drive
F003 Max. output frequency
Range: 50.00~400.00Hz
【
50.00
】
Max. output frequency is the highest frequency output from the drive, see
fmax in Figure 6-3;
Rated frequency (also called base frequency) is the minimum output
frequency at the rated voltage, see fb in Figure 6-3. If the base frequency is
set too low, motor overheat may occur or even be damaged when operating
at it for a long time;
Generally, rated voltage is set at the motor's rated voltage.
f
max
Output volt
f
b
f
H
f
L
Output
Freq.
Vrated
Figure 6-3 Illustration of characteristic parameters
F004 Running direction selection
Range: 0
、
1
【
0
】
Motor's running direction can be changed by setting F004. The motor's
running direction is determined after the motor is wired correctly. You can
change the setting of F004 to change the direction without rewiring the motor.
0: Same with preset direction
1: Reverse to preset direction
TD3200 Variable Speed Drive for Elevator Door Control User Manual