E300 Design Guide 131
Issue Number: 1
A06 (Profile Speed J39)
(Actual Speed J40)
Open loop mode Profile speed
This indicates the profile generator output speed in mm/s units. The profile generator output speed is based on the profile specified in menu G-Profile
parameters.
RFC-A and RFC-S mode Actual speed
This parameter indicates the actual speed of the motor in mm/s units. In closed loop operation the actual speed is based upon the encoder feedback
and motor rated speed mm/s and rpm scaling.
A07 (Output Power J59)
The Output power is the power flowing via the AC terminals of the drive. The power is derived as the dot product of the output voltage and current
vectors, and is therefore correct even if the motor parameters are incorrect and the motor model does not align the reference frame with the flux axis
of a motor in RFC-A mode. For Open loop, RFC-A and RFC-S modes a positive value of power indicates power flowing from the drive to motor.
A08 (Output Frequency J60)
The Output frequency in Open loop mode is the sum of the post ramp reference and the motor slip compensation frequency. In Closed loop operation
the output frequency is not controlled directly and the output frequency is a measurement of the frequency applied to the motor.
A09 (Output Voltage J61)
The Output voltage is the rms line to line voltage at the AC output terminals (UVW) of the drive.
A06 {J39} Profile Speed (OL)
{J40} Actual Speed (RFC)
RO Num ND NC PT
OL
Ú
0 to 10000 mm/s
Ö
RFC-A
Ö
RFC-S
Ö
A07 {J59} Output Power
RO Num ND NC PT FI
OL
Ú
+ VM_POWER kW
Ö
RFC-A
Ö
RFC-S
Ö
A08 {J60} Output Frequency
RW Num ND NC PT FI
OL
Ú
+ VM_SPEED_FREQ _
REF Hz
Ö
RFC-A
+
550.0 Hz
Ö
RFC-S
Ö
A09 {J61} Output Voltage
RO Num ND NC PT FI
OL
Ú
+ VM_AC_VOLTAGE V
Ö
RFC-A
Ö
RFC-S
Ö