E300 Design Guide 211
Issue Number: 1
See Motor Thermal Time Constant 1 (B20).
See Motor Thermal Time Constant 1 (B20).
See Motor Thermal Time Constant 1 (B20).
See Motor Thermal Time Constant 1 (B20).
If Reverse Motor Phase Sequence (B26) = 0 the output phase sequence is U-V-W when Output Frequency (J60) is positive and W-V-U when Output
Frequency (J60) is negative. If Reverse Motor Phase Sequence (B26) = 1 the output phase sequence is reversed so that the phase sequence in W-
V-U for positive frequencies and U-V-W for negative frequencies.
Fast Disable (B27) normally shows the hardware enable state based on the state of the safe torque off system. However, drive I/O can be routed to
Fast Disable (B27) to reduce the disable time. See description of the enable logic for more details.
Value Text
0 Power down
1Zero
2 Real time
B22 Motor Thermal Time Constant 2
Mode Open-loop: RFC-A, RFC-S
Minimum 1.0 Maximum 3000.0
Default 89.0 Units s
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 1
Coding RW
B23 Motor Thermal Time Constant 2 Scaling
Mode Open-loop: RFC-A, RFC-S
Minimum 0 Maximum 100
Default 0 Units %
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW
B24 Rated Iron Losses As Percentage Of Losses
Mode Open-loop: RFC-A, RFC-S
Minimum 0 Maximum 100
Default 0 Units %
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW
B26 Reverse Motor Phase Sequence
Mode Open-loop: RFC-A, RFC-S
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW
B27 Fast Disable
Mode Open-loop: RFC-A, RFC-S
Minimum 0 Maximum 1
Default Units
Type 1 Bit Volatile Update Rate 2 ms read
Display Format Standard Decimal Places 0
Coding RO, ND, NC, PT