Maximum Deadtime Compensation (B46) is the deadtime compensation used to compensate for dead-time effects in the inverter. This level of 
compensation is used when the drive output current is above Current At Maximum Deadtime Compensation (B47). Both of these values related to 
dead-time compensation are measured during auto-tuning and cannot be set by the user. It should be noted that if the auto-tuning test is not 
performed and Maximum Deadtime Compensation (B46) = 0 then dead-time compensation is disabled. Although it is not recommended, it is possible 
to disable dead-time compensation by setting Disable Deadtime Compensation (B48) = 1.
See Maximum Deadtime Compensation (B46).
See Maximum Deadtime Compensation (B46).
See Motor Autotune (B11)
B46 Maximum Deadtime Compensation
Mode Open-Loop, RFC-A, RFC-S
Minimum 0.000 Maximum 10.000
Default 0.000 Units us
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 3
Coding RO, NC, PT
B47 Current At Maximum Deadtime Compensation
Mode Open-Loop, RFC-A, RFC-S
Minimum 0.00 Maximum 100.00
Default 0.00 Units %
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 2
Coding RO, NC, PT
B48 Disable Deadtime Compensation
Mode Open-Loop, RFC-A, RFC-S
Minimum 0 Maximum 1
Default 0 Units
Type 1Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW
B49 Disable Deadtime Compensation
Mode RFC-A, RFC-S
Minimum 0 Maximum 100
Default 0 Units %
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW